25 / 2024-03-28 13:22:04
Prestrike Characteristics of a Vacuum Interrupter in Controlled Switching of Shunt Capacitor Banks
controlled switching,transient breakdown voltage,power frequency voltage,fast vacuum circuit breaker(FVCB)
Draft Accepted
Yuqian Niu / Xi’an Jiaotong University
Siyi Wei / Xi'an Jiaotong University
Feiyue Ma / Xi’an Jiaotong University;Research Institute of State Grid Ningxia Electric Power Co., ltd., Yinchuan,
Shangpeng Sun / Research Institute of State Grid Ningxia Electric Power Co., ltd., Yinchuan
Xiaofei Yao / xi'an jiaotong university
Xiaojing Zuo / State Grid Jibei Marketing Service Center
Zhiyuan Liu / Xi’an Jiaotong University;State Key Laboratory of Electric Power Equipment
Yingsan Geng / Xi’an Jiaotong University;State Key Laboratory of Electric Power Equipment
Jianhua Wang / Xi'an Jiaotong University
 Controlled switching of shunt capacitor banks could effectively moderate the transient electromagnetic impact on the power grid, which requires an accurate making or breaking operation for the engaged circuit breakers. The objective of this study is to experimentally determine the prestrike characteristics of a vacuum interrupter in making against a power-frequency voltage. A 12 kV fast vacuum circuit breaker (FVCB) is used. The closing velocities, defined as an average velocity over a 1/2 contact gap before the contact mating, is set as 1.43 m/s. The transient breakdown voltage values are recorded under different kinds of voltage-wave phase-angle conditions. In each experimental case, the contact of the test vacuum circuit breaker is supposed to metal-mate at different voltage-wave phase angles, which rise from 0° to 150° and are stepped by 30°. Results show that the transient breakdown process in making the power frequency voltage is different from those of gas switches or vacuum interrupters under DC voltage. The latter two methods are traditionally taken as solutions for determining the controlled-making strategy of the capacitor banks. The study contributes to the promotion of the controlled vacuum-switching technology.
Important Date
  • Conference Date

    Nov 10

    2024

    to

    Nov 13

    2024

  • Nov 11 2024

    Draft paper submission deadline

  • Nov 19 2024

    Registration deadline

Sponsored By
Xi’an Jiaotong Universit