Test Study of Water Quantity Loss of Cooling Tower on U - Type Liquidometer
wet cooling tower; U-tube liquidometer; law of water quantity loss of cooling tower; law of evaporation loss; law of drift loss
Draft Pending
Baohong Song / Guizhou Colorful Sunshine Water Co., Ltd
By changing the data acquisition mode of the wet cooling tower collecting basin liquid level, studied the law of water quantity loss of cooling tower. The water quantity loss of cooling tower was measured by U-tube liquidometer, real-time and accurate water quantity loss data were obtained. When the liquid level of collecting basin drops 1mm, the water quantity loss of one cooling tower is 1.38 m3. In stable engineering application operation and under different environmental and climatic conditions, the water quantity loss was between 84.7-144 m3 h-1. Through the accurate measurement of water loss and the established of water quantity loss law of cooling tower, and therefore, evaporation loss and drift loss can be analyzed conveniently and accurately. Thus kindly the hypothesis of Michael model is proved that the air in the tower is saturated air. And the laws for variation in evaporative loss and drift loss of the cooling tower were established. The testing and theoretical analysis of water quantity loss by the application of the test device will be widely used in the design and other related engineering fields, such as the control and research of water quantity loss of wet cooling tower and the drift recovery.
Important Date
  • Conference Date

    Oct 21

    2019

    to

    Oct 25

    2019

  • Oct 20 2019

    Draft paper submission deadline

  • Oct 25 2019

    Registration deadline

Organized By
Zhejiang University(ZJU)
Kunming University of Science and Technology(KUST)
Contact Information