696 / 2019-04-22 17:05:53
Fault disappearing judgement of single phase grounding in neutral point non-effective grounding system based on adjustable resistor
current change rate,fault disappearing judgement,neutral point non-effective grounding system,adjustable resistor
Final Paper
Bozhong Pan / Key Laboratory of Power System Intelligent Dispatch and Control (Shandong University)
Wei Cong / Key Laboratory of Power System Intelligent Dispatch and Control (Shandong University)
Yanfei Ma / State Grid Shandong Electric Power Company Jinan, China
In the distribution network, it is important to determine whether single phase grounding fault has disappeared in time. The reason is that accurate determination contribute to improving safety of system operation and reliability of power supply. This paper proposed a method to judge the disappearance of single phase ground fault based on neutral point non-effective grounding system by means of adjustable resistor. When single phase grounding occurs, forcibly grounding the fault phase at the busbar could reduce fault point voltage and reduce high residual voltage hazard. Then adjust the value of adjustable resistor at the busbar grounding branch, and then monitor the trend of grounding branch current to determine if the fault has disappeared. Simulation results show that the proposed method can accurately and timely judge whether single phase grounding fault disappears.
Index Terms--adjustable resistor, current change rate, fault disappearing judgement, neutral point non-effective grounding system.
Important Date
  • Conference Date

    Oct 21

    2019

    to

    Oct 24

    2019

  • Oct 13 2019

    Abstract Notification of Acceptance

  • Oct 13 2019

    Draft paper submission deadline

  • Oct 14 2019

    Draft Paper Acceptance Notification

  • Oct 24 2019

    Registration deadline

  • Oct 29 2019

    Final Paper Deadline

Organized By
Xi'an Jiaotong University
Contact Information