An Accident Analysis of Circuit Breaker in HVDC Converter Station Filter Branch
ID:215 View Protection:ATTENDEE Updated Time:2020-11-11 12:10:06 Hits:311 Poster Presentation

Start Time:Pending(12)

Duration:Pending

Session:No Session »

No files

Abstract
In the HVDC transmission systems, AC filter circuit breakers (CB) are switched frequently to keep the balance of reactive power. CB stays under AC/DC hybrid conditions since the current flowing through AC filter is capacitive. Moreover, due to the differences between the resistances of multiple breaks, the unbalanced voltage distribution is easy to occur, which will cause a high transient overvoltage on one break among them. In recent years, the circuit breaker explosion accidents have occurred many times. In this paper, a real case of the AC filter arc fault is briefly described. Based on PSCAD, a simulation model is established for CB and dynamic arcing resistance. The combination of simulation results and strip inspections of on-site CB confirms the reasons for the arc fault and provides a basis for the operation and maintenance of AC filter in HVDC converter stations.
Keywords
arc fault,AC filter,dynamic arc model,overvoltage,circuit breaker
Speaker
Junbo Deng
Xi'an Jiaotong University

Submission Author
Chunying HE Xi'an Jiaotong University
Xiaoguang Zhu Xi'an Jiaotong University
Junbo Deng Xi'an Jiaotong University
Xiaohui Chen Xi'an Jiaotong University
Yubo Guo Xi'an Jiaotong University
Submit Comment
Verify Code Change Another
All Comments
Important Date
  • Conference Date

    Oct 21

    2019

    to

    Oct 24

    2019

  • Oct 13 2019

    Abstract Notification of Acceptance

  • Oct 13 2019

    Draft paper submission deadline

  • Oct 14 2019

    Draft Paper Acceptance Notification

  • Oct 24 2019

    Registration deadline

  • Oct 29 2019

    Final Paper Deadline

Organized By
Xi'an Jiaotong University
Contact Information