An Accident Analysis of Circuit Breaker in HVDC Converter Station Filter Branch
ID:215
View Protection:ATTENDEE
Updated Time:2020-11-11 12:10:06 Hits:311
Poster Presentation
Abstract
In the HVDC transmission systems, AC filter circuit breakers (CB) are switched frequently to keep the balance of reactive power. CB stays under AC/DC hybrid conditions since the current flowing through AC filter is capacitive. Moreover, due to the differences between the resistances of multiple breaks, the unbalanced voltage distribution is easy to occur, which will cause a high transient overvoltage on one break among them. In recent years, the circuit breaker explosion accidents have occurred many times. In this paper, a real case of the AC filter arc fault is briefly described. Based on PSCAD, a simulation model is established for CB and dynamic arcing resistance. The combination of simulation results and strip inspections of on-site CB confirms the reasons for the arc fault and provides a basis for the operation and maintenance of AC filter in HVDC converter stations.
Keywords
arc fault,AC filter,dynamic arc model,overvoltage,circuit breaker
Submission Author
Chunying HE
Xi'an Jiaotong University
Xiaoguang Zhu
Xi'an Jiaotong University
Junbo Deng
Xi'an Jiaotong University
Xiaohui Chen
Xi'an Jiaotong University
Yubo Guo
Xi'an Jiaotong University
Submit Comment