A Fault Location Algorithm for HVDC Grounding Electrode Line with Distribution parameter model
ID:312 View Protection:ATTENDEE Updated Time:2020-11-11 12:10:27 Hits:371 Poster Presentation

Start Time:Pending(12)

Duration:Pending

Session:No Session »

No files

Abstract
When taking earth as part of HVDC system loop, Grounding electrode system is connected to ground effectively, operation mode of which is different from normal HVDC lines. A ±500kV HVDC system model is established in this paper by using PSCAD/EMTDC simulation platform, based on which the fault operation characteristic of grounding electrode line is simulated and analyzed , and a fault location method based on the Bergeron line model aimed at single line grounded short circuit is also put forward in this paper. Head-end voltage and two outlets current after fault are used to calculate voltage distribution along line. According to the characteristics that the fault or electrode point is the minimum voltage along line, the fault location function is established to calculate the fault distance. The simulation result and project instances indicated that the fault of grounding electrode line can be located accurately with the proposed method.
Keywords
HVDC;,grounding electrode line,Bergeron line model,fault location,voltage distribution
Speaker
Yining Zhang
CSG EHV

Submission Author
Yining Zhang CSG EHV
Xingxing Cheng Jiaxing Power Supply Company State Grid Corporation of China Jiaxing, China
Submit Comment
Verify Code Change Another
All Comments
Important Date
  • Conference Date

    Oct 21

    2019

    to

    Oct 24

    2019

  • Oct 13 2019

    Abstract Notification of Acceptance

  • Oct 13 2019

    Draft paper submission deadline

  • Oct 14 2019

    Draft Paper Acceptance Notification

  • Oct 24 2019

    Registration deadline

  • Oct 29 2019

    Final Paper Deadline

Organized By
Xi'an Jiaotong University
Contact Information